Views: 976 Author: Site Editor Publish Time: 2020-01-03 Origin: Site
1 Unit Perkins 1200kw Prime Diesel Generator
General Features:
Engine ( Perkins 4012-46 TAG2A )
Radiator 50℃ max,fans are driven by belt, with safety guard
24V charge alternator
Alternator: single bearing alternator IP23,insulationclass H/H
Absorber
Dry type air filter, fuel filter, oil filter, coolant filter
Main line circuit breaker
Standard control panel
batteries, rack and cable
Ripple flex exhaust pipe, exhaust siphone, flange,
muffler
User manual
Perkins 1200kw Prime Diesel Generator Prime Power (PRP): Prime power is available for an unlimited number of annual hours in variable
load application, in accordance with GB/T2820-97(eqvISO8528); A 10% overload capability is available
for a period of 1 hour within a 12-hour period of operation.
Perkins 1200kw Prime Diesel Generator Standby Power Rating (ESP): The standby power rating is applicable for supplying emergency power
for the duration of a utility power interruption. No overload, utility parallel or negotiated outage operation
capability is available at this rating.
Perkins 1200kw Prime Diesel Generator Warranty:
Hiersun Power provides a full line of brand new and high quality products. Each and every unit is
strictly factory tested. Warranty is according to our standard conditions: 12 months or 1,000 running hours, subject to theearlier one.Service and parts are available from Hiersun Power or distributors in your location.
Perkins 1200kw Prime Diesel Generator ENGINE DATA
Manufacturer / Model: Perkins 4012TAG2A,4-cycle
Air Intake System: Turbo, Air/Air cooling
Fuel Injection System: Direct Injection
Cylinder Arrangement: 12 in “V”
Displacement: 45.842L
Bore and Stroke: 160×190(mm)
Compression Ratio: 13.6
Rated RPM: 1500rpm
Max. Standby Power at Rated RPM: 1437KW/1955HP
Governor Type: Electronic
Exhaust System
Exhaust Gas Flow(after turbo): 315m3/min
Exhaust Temperature: 450℃
Max Back Pressure: 6.12kPa
Air Intake System
Max Intake Restriction: 3.8kPa
Consumption: 128m3/min
Air Flow: 1308m3/min
Prime Power) Load: 200 g/Kwh
75%(Prime Power) Load: 201 g/Kwh
50%(Prime Power) Load: 203 g/Kwh
100%( Prime Power) Load: 295.1L/h
Oil System
Oil Consumption: 0.52g/KWhr
Engine Oil Tank Capacity: 159L
Min Oil Pressure at Rated RPM: 340kPa
Cooling System
Total Coolant Capacity: 212L
Thermostat: 71-85℃
Max Water Temperature: 96℃
Perkins 1200kw Prime Diesel Generator Alternator Data
Number of Phase: 3
Connecting Type: 3 Phase and 4 Wires, “Y” type connecting
Number of Bearing: 1
Power Factor: 0.8
Protection Grade: IP23
Altitude: ≤1000m
Exciter Type: Brushless, self-exciting
Insulation Class, Temperature Rise: H/H
Telephone Influence Factor (TIF): <50
THF: <2%
Alternator Capacity: 1550KVA
Alternator Efficiencies: 95.7%
For more information about this unit, please contact us.